前言 大家好,我是林总, 咨询UPS电源的空开配置与线缆选型,今天分享一套汇报表格,可以参考。 正文 模块化三进三出系列
3-2-1、(10-200KVA)空开配置
|
功率 |
电池 电压 |
输入电流A |
输出电流A |
电池电流A |
输入空开A |
输出空开A |
电池空开A |
|
10KVA |
768VDC |
16 |
15 |
13 |
25/3P |
16/3P |
16/3P |
|
20KVA |
768VDC |
32 |
30 |
25 |
63/3P |
32/3P |
25/3P |
|
30KVA |
768VDC |
48 |
45 |
38 |
63/3P |
63/3P |
63/3P |
|
40KVA |
768VDC |
64 |
61 |
50 |
100/3P |
63/3P |
63/3P |
|
50KVA |
768VDC |
80 |
76 |
63 |
100/3P |
100/3P |
63/3P |
|
60KVA |
768VDC |
96 |
91 |
75 |
100/3P |
100/3P |
100/3P |
|
70KVA |
768VDC |
112 |
106 |
88 |
125/3P |
125/3P |
100/3P |
|
80KVA |
768VDC |
128 |
121 |
100 |
160/3P |
125/3P |
125/3P |
|
90KVA |
768VDC |
144 |
136 |
113 |
160/3P |
160/3P |
125/3P |
|
100KVA |
768VDC |
159 |
151 |
125 |
160/3P |
160/3P |
125/3P |
|
110KVA |
768VDC |
175 |
167 |
138 |
200/3P |
160/3P |
160/3P |
|
120KVA |
768VDC |
191 |
182 |
150 |
200/3P |
200/3P |
160/3P |
|
130KVA |
768VDC |
207 |
197 |
163 |
250/3P |
200/3P |
160/3P |
|
140KVA |
768VDC |
223 |
212 |
175 |
250/3P |
250/3P |
200/3P |
|
150KVA |
768VDC |
239 |
227 |
188 |
250/3P |
250/3P |
200/3P |
|
160KVA |
768VDC |
255 |
242 |
201 |
250/3P |
250/3P |
200/3P |
|
170KVA |
768VDC |
271 |
258 |
213 |
320/3P |
250/3P |
250/3P |
|
180KVA |
768VDC |
287 |
273 |
226 |
320/3P |
320/3P |
250/3P |
|
190KVA |
768VDC |
303 |
288 |
238 |
320/3P |
320/3P |
250/3P |
|
200KVA |
768VDC |
319 |
303 |
251 |
320/3P |
320/3P |
250/3P |
注:
l 实际开关容量不得小于表中开关容量;
l 电池开关额定工作直流电压,不得低于768VDC。
3-2-2、(10-200KVA)电缆配置
|
功率 |
输入电缆mm2 |
输出电缆mm2 |
电池电缆mm2 |
零线 mm2 |
地线 mm2 |
备注 |
|
10KVA |
6 |
6 |
6 |
6 |
6 |
|
|
20KVA |
10 |
10 |
10 |
10 |
6 |
|
|
30KVA |
10 |
10 |
10 |
10 |
6 |
|
|
40KVA |
16 |
16 |
16 |
16 |
10 |
|
|
50KVA |
25 |
25 |
16 |
25 |
10 |
|
|
60KVA |
25 |
25 |
25 |
25 |
10 |
|
|
70KVA |
25 |
25 |
25 |
25 |
10 |
|
|
80KVA |
35 |
35 |
25 |
35 |
16 |
|
|
90KVA |
35 |
35 |
35 |
35 |
16 |
|
|
100KVA |
50 |
50 |
50 |
50 |
25 |
|
|
110KVA |
50 |
50 |
50 |
50 |
25 |
|
|
120KVA |
70 |
70 |
50 |
70 |
35 |
|
|
130KVA |
70 |
70 |
70 |
70 |
35 |
|
|
140KVA |
70 |
70 |
70 |
70 |
35 |
|
|
150KVA |
70 |
70 |
70 |
70 |
35 |
|
|
160KVA |
70 |
70 |
70 |
70 |
35 |
|
|
170KVA |
95 |
95 |
70 |
95 |
35 |
|
|
180KVA |
95 |
95 |
95 |
95 |
35 |
|
|
190KVA |
95 |
95 |
95 |
95 |
35 |
|
|
200KVA |
95 |
95 |
95 |
95 |
35 |
注:
l 实际电缆线径不得小于表中线径;
l电缆的截面积是按铜芯电缆计算的(如果用铝芯电缆则需增加30%)同时考虑了温度的上升以及最多15米(交流回路)或10米(直流回路)的线路压降。如果线路更长,则要选用截面积更大的电缆(具体可向技术支持部咨询),以保证线路的压降低于3%(交流)或1%(直流);
特别说明:考虑到日后扩容的方面,模块化UPS的线缆、空开配置,一般按机柜最大功率配置。